Addressable photoelectric smoke detector AW-ASD2188
Technical parameters:
- Executive standard: GB4715-2005
- Operating voltage: 24V (pulse modulation)
- Operating current: <300uA (monitoring status) or <1.5mA (alarm status)
- Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status.
- Weight: about 70g
- External dimensions: diameter: 100mm, height: 55mm (with the base)
- Wiring method: non-polarity two-bus system (L1, L2)
- Operating environment: Indoor, temperature: - 10 ℃ ~ +55 ℃ ; relative humidity: ≤95% (40℃±2℃, without condensation)
- Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection.
- Installation height: ≤12m
- Protection area: about 60m2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System
- Matched host machine: fire alarm control panel (such as AW-AFP2188)
Addressable fixed temperature heat detector AW-ATD2188
Technical parameters:
- Executive standard: GB4716-2005
- Operating voltage: 24V (pulse modulation)
- Operating current: <300uA (monitoring status) or <1.5mA (alarm status)
- Work indication: The red indicator will blink in the monitoring status or remain lit in the alarm status.
- Weight: about 47g
- Product class: A2
- External dimensions: diameter: 100mm, height: 56mm (with the base)
- Wiring method: non-polarity two-bus system (L1, L2)
- Operating environment: Indoor, temperature: - 10 ℃ ~ +50 ℃ ; relative humidity: ≤95% (40℃±2℃, without condensation)
- Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection.
- Installation height: ≤8m
- Protection area: about 60m2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System.
- Matched host machine: fire alarm control panel (such as AW-AFP2188)
Addressable smoke and heat combined detector AW-ASH2188
Technical parameters:
- Executive standard: GB 4715-2005,GB4716-2005
- Operating voltage: 24V (pulse modulation)
- Operating current: ≤0.5mA (monitoring status) or <1.5mA (alarm status)
- Sensing technology: the use of photoelectric sensors and temperature sensors dual sensor technology, thermal type: A2
- Weight: about 100g
- Encoding: Electronic, coding range is 1 to 324
- External dimensions: diameter: 100mm, height: 55mm (with the base)
- Wiring: Promise of wire
- LED: red, blinking about once every 12 seconds when the patrol, alarm always
- Operating environment: Indoor, temperature: - 10 ℃ ~ +50 ℃; relative humidity: ≤95% (40℃±2℃, without condensation)
- Installation height: ≤8m
- Shell Material: ABS
- Protection area: about 60m2. For details, see related provisions in GB50116-98 Code for Design of Automatic Fire Alarm System.
- Matched host machine: fire alarm control panel (such as AW-AFP2188)