Tampilkan postingan dengan label Heat. Tampilkan semua postingan
Tampilkan postingan dengan label Heat. Tampilkan semua postingan

Sabtu, 20 Juni 2015

AW Conventional Detector

Conventional photoelectrismoke detector
Item
Parameters
Operating Voltage Range:
to 32 VDC Volts Non-polarized
Standby Current:
100µA 24 VDC
Maximum Alarm Current (LED on: )
55mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Adjustable Sensitivity:
1-2.5%/FT
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Conventional fitemperature heat detector


Model No.: AW-CTD805

Item
Parameters
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Installation Temperatures:
14°F to 122°F (-10°C to50°C)
Operating Humidity Range:
10% to 93% RelativHumidity Non-condensing
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
40µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Fixed Temperature Rating:
135°F (57°C)

Conventional smoke and heat combined detector

Model No.: AW-CSH202


Item
Parameters
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
60µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Smoke    Sensitivity:
1.06±.26%FT.
Fixed Temperature Rating:
135°F (57°C)
Rate of Rise Detection:
Responds to greater than 15°F/min
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)



UV flame detector
AW-FD602-UV

SPECIFICATIONS
Operating Voltage Range:                    12 to 30 VDC Volts
Standby Current:                                  10 mA @ 24 VDC Alarm Current                                      30 mA @ 24 VDC Spectrum:                                           180~290nm
Detection Angle:                                 110 degree
Detection Sensitivity:                         Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol )
Relay Contact Load:                            1A@DC24V
Normal Status:                                     LED blinking in 5 seconds interval
Alarm Status:                                       LED lit steady
Protection rating:                                  IP 32
Operating Humidity Range:                10% to 93% Relative HumidityNon-condensing
Operating Temperature Range:          -10°C to 50°C (14°F to 122°FHeight:                                                 1.8˝ (45 mminstalled in BasDiameter:                                              4.0˝ (103 mm)


Weight:                                                 5.4 oz. (153g)

AW Addressable Detector

Addressable photoelectric smokdetector AW-ASD2188

Technical parameters:

  1. Executive standard: GB4715-2005
  2. Operating voltage: 24V (pulse modulation)
  3. Operating current: 300uA (monitoring status) or 1.5mA (alarm status)
  4. Work indication: The red indicator will blink in the monitoring status or remailit in the alarm status.
  5. Weight: about 70g
  6. Externadimensions: diameter: 100mm, height: 55mm (with the base)
  7. Wiring method: non-polarity two-bus system (L1, L2)
  8. Operatin environment Indoor temperature  10   +55   relativhumidity: 95% (40±2, without condensation)
  9. Coding mode: It can realize electronic coding via coder in situ. Address code1 to 324 are available for selection.
  10. Installation height: 12m
  11. Protection   area:   about   60m2.   For   details,   see   related   provisions   iGB50116-98 Code for Design of Automatic Fire Alarm System
  12. Matched host machine: fire alarm contropane(such as AW-AFP2188)

Addressable fixed temperature heat detectoAW-ATD2188

Technical parameters:

  1. Executive standard: GB4716-2005
  2. Operating voltage: 24V (pulse modulation)
  3. Operating current: 300uA (monitoring status) or 1.5mA (alarm status)
  4. Work indication: The red indicator will blink in the monitoring status or remailit in the alarm status.
  5. Weight: about 47g
  6. Product class: A2
  7. Externadimensions: diameter: 100mm, height: 56mm (with the base)
  8. Wiring method: non-polarity two-bus system (L1, L2)
  9. Operatin environment Indoor temperature  10   +50  relativhumidity: 95% (40±2, without condensation)
  10. Coding mode: It can realize electronic coding via coder in situ. Address codes 1 to 324 are available for selection.
  11. Installation height: 8m
  12. Protectio area abou 60m2 Fo details,  se relateprovisions iGB50116-98 Code for Design of Automatic Fire Alarm System.
  13. Matched host machine: fire alarm contropane(such as AW-AFP2188)

Addressable smoke and heat combined detectoAW-ASH2188

Technical parameters:

  1. Executive standard: GB 4715-2005,GB4716-2005
  2. Operating voltage: 24V (pulse modulation)
  3. Operating current: 0.5mA (monitoring status) or 1.5mA (alarm status)
  4. Sensin technology th use  o photoelectri sensor an temperatursensordual sensor technology, thermatype: A2
  5. Weight: about 100g
  6. Encoding: Electronic, coding range is 1 to 324
  7. Externadimensions: diameter: 100mm, height: 55mm (with the base)
  8. Wiring: Promise of wire
  9. LED: red, blinking about once every 12 seconds when the patrol, alaralways
  10. Operatin environment Indoor temperature  10   +50 ; relativhumidity: 95% (40±2, without condensation)
  11. Installation height: 8m
  12. ShelMaterial: ABS
  13. Protectio area abou 60m2 Fo details,  se relate provisioniGB50116-98 Code for Design of Automatic Fire Alarm System.
  14. Matched host machine: fire alarm contropane(such as AW-AFP2188)