Conventional fire alarm control panel

Introduction:


1.    AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2.    It is modularized design, the panel can extend from 1 zonto 32 zones easily.
3.    It has 2 level control mode by lock
4.    It has 24VDC an5VDC power supply output.
5.    It has FIRE and FAULT signal output.
6.    It has 2 general sounderoutput.
7.    Each zone has 1 circuit detectorinput .
8.    Each zone can be disable by a button.
9.    It has RESET button treset the panel.
10.  It has SILENCE button to stop BUZZER and SOUNDERS.
11.  It has EVACUATE button to start manual fire alarm immediately.
12.  It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13.  It has an optional GSM modulfor fire alarm by SMS .
14.  It is economic, user-friendly and easy maintenance.
ITEM
1Zone panel
2Zone panel
4-8 Zone panel
12-32 Zone
panel
Model No.
AW-CFP2166-01
AW-CFP2166-02
AW-CFP2166-04
-8
AW-CFP2166-12-
32
Power specification

Mains supply voltage
110VAC or 240VAC
Internal power supply
27.2VDC
Total output current limited
500mA @
240VAC
500mA @
240VAC
3A @ 240VAC
3A @ 240VAC
Main supply monitor for fault
Yes
Battery protection for low voltage
Yes
Batteries (default configuration)
12V2AH*2
Detector circuit specification

Number of circuit
1
2
4-16
4-32
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Line fault monitor for detector
removal
Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes
Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted
to give Detector Removal Fault)
Call point resistor value
470 to 680  Ω , 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone
20 (based on a total detector current of 2mA, each detector consuming 100μ
A).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call
points per zone
No limit
Sounder circuit specification

Number of general circuits
2
End of line resistor value
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Outputs fused AT
400mA
Maximum number of bells @ 20mA
of each sounder output
20
Fuses

Battery fuse
1.5A F 20mm
Sounder outputs
500mA F 20mm
Fire and fault output