Conventional fire alarm control panel
Introduction:
1. AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2. It is modularized design, the panel can extend from 1 zone to 32 zones easily.
3. It has 2 level control mode by a lock
4. It has 24VDC and 5VDC power supply output.
5. It has FIRE and FAULT signal output.
6. It has 2 general sounders output.
7. Each zone has 1 circuit detectors input .
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. It has SILENCE button to stop BUZZER and SOUNDERS.
11. It has EVACUATE button to start a manual fire alarm immediately.
12. It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13. It has an optional GSM module for fire alarm by SMS .
14. It is economic, user-friendly and easy maintenance.
ITEM
|
1Zone panel
|
2Zone panel
|
4-8 Zone panel
|
12-32 Zone
panel
|
Model No.
|
AW-CFP2166-01
|
AW-CFP2166-02
|
AW-CFP2166-04
-8
|
AW-CFP2166-12-
32
|
Power specification
|
||||
Mains supply voltage
|
110VAC or 240VAC
|
|||
Internal
power supply
|
27.2VDC
|
|||
Total output current
limited
|
500mA @
240VAC
|
500mA @
240VAC
|
3A @ 240VAC
|
3A @ 240VAC
|
Main supply monitor
for fault
|
Yes
|
|||
Battery protection for
low voltage
|
Yes
|
|||
Batteries (default configuration)
|
12V2AH*2
|
|||
Detector circuit
specification
|
||||
Number of circuit
|
1
|
2
|
4-16
|
4-32
|
Line fault monitor
for open circuit
|
Yes
|
|||
Line fault monitor
for short circuit
|
Yes
|
|||
Line fault monitor
for detector
removal
|
Yes, if End
of Line Monitor Unit
fitted in place of
End of Line Resistor
|
|||
End of Line device
|
6.8k Ω ,5% tolerance, 0.25W (colour
code-blue,grey,red,gold)
|
|||
Detector continuity diodes
|
Silicon
1N4001 or Schottky type (required if
End of Line Monitor Unit
fitted
to give Detector
Removal Fault)
|
|||
Call point resistor value
|
470 to 680 Ω , 0.225 or
0.5 watt
|
|||
Maximum number of smoke/heat
detectors per zone
|
20 (based on
a total detector current of 2mA, each
detector consuming 100μ
A).Note: if End
of Line Monitor Unit is
fitted, for correct operation maxmum
voltage
drop must not exceed
12 volts.
|
|||
Maximum number of
manual call
points per
zone
|
No limit
|
|||
Sounder circuit specification
|
||||
Number of general circuits
|
2
|
|||
End of line
resistor value
|
6.8k Ω ,5% tolerance, 0.25W (colour
code-blue,grey,red,gold)
|
|||
Line fault monitor
for open circuit
|
Yes
|
|||
Line fault monitor
for short circuit
|
Yes
|
|||
Outputs fused AT
|
400mA
|
|||
Maximum number of
bells @ 20mA
of each sounder
output
|
20
|
|||
Fuses
|
||||
Battery fuse
|
1.5A F 20mm
|
|||
Sounder outputs
|
500mA F 20mm
|
|||
Fire and fault output
|
||||