Tampilkan postingan dengan label Manual call point. Tampilkan semua postingan
Tampilkan postingan dengan label Manual call point. Tampilkan semua postingan

Sabtu, 20 Juni 2015

AW Conventional in-out

Entrance LED
Manual Call Point


Parameters
AW-CMC2166-1(Break glass)

  • Working voltage: 220VAC/50Hz or 24VDC
  • Maximum current5A (220VAC/50Hz) or 8A(24VDC)
  • Contactor resistance: 0.
  • Working temperature: -10~+50 
  • Relative humidity: max 93±2%

Alarm Bell




Model No.


Diameter


Work voltage
Work current  @
24VDC


Volume(dB)
AW-CBL2166-A-4
4 (100mm)
DC6V DC12V DC24V AC110V
AC230V



25  mA
85
AW-CBL2166-A-6
6(150mm)
95
AW-CBL2166-A-8
8(200mm)
97

AW-CBL2166-A-10
10(250mm)

100

Strobe Horn/Hooter


AW-CSS2166-2
Work Voltage
DC20V-DC30V
Work Current (average)
95mA
Flasintensity
1.2WS
Flascycle
<2.0s
Flasher life
30000times
Max alarm volume
100dB
Alarm voice
A: pokice car
B: Fire Truck ( default) C: Ambulance
Size
160*128*54mm
134*115*48mm

AW Addressable In-Out Modul

Addressable manual call point AW-AMC2188

Technical parameters:

  1. Executive standard: GB19880-2005
  2. Operating voltage: 24V (pulse modulation)
  3. Operating current: 300uA (in the monitoring status); 2mA (in the actiostatus)
  4. Output contact: Normally open contact; capacity: 0.1A/30VDC
  5. Weight: About 120g
  6. Wiring method: nonpolar two-bus system (L1, L2)
  7. Operatin environment Indoor temperature  10    50   relativhumidity: 95% (40±2, without condensation)
  8. Coding method: It can realize online coding with the help of a coder anwithout the necessity of disassembling the bus (however, the equipmenmust be powered off). Address codes 1 to 324 are available for selection.
  9. Telephone jack: Two-wire fire telephone jack (equipped with a standard Ф 6.3 single-track audio connector).
  10. Starting part: A plastipressing sheet that may be used repeatedly. It can bmanually reset with a speciatooafter being pressed.
  11. Starting mode: Press the pressing sheet manually.
  12. Indicator: The red ALARM indicator will blink in the inspection status oremain lit in the alarm status; the PHONE indicator will blink when a firtelephone loop is connected, otherwise it wilbe out.
  13. Matched host machine: fire alarm contropane(such as AW-AFP2188)

Addressable hooter/horn AW-ASS2188

Technical parameters:

  1. Executive standard: GA385- 2002
  2. Operating voltage: DC24V (pulse modulation)
  3. Operating current: quiescent current: 1mA (the current consumed by thbus); alarm current: 120mA@DC24V
  4. Operating environment: Temperature: 10+55; relative humidity: 95(40, without condensation)
  5. Flushing rate: one time/s
  6. Alarm volume: 85dB (measured at a place 3m in front of the hooter/horn)
  7. Coding method: Electronic coding
  8. Wiring method: Four-wire system, non-polarity two signabuses (L1, L2) anpower line(+24V, GND)
  9. Matched host machine: fire alarm contropane(such as AW-AFP2188)

Addressable input module AW-AIO2188-IN

Features and technical parameters:
  1. Mode of operation: Nonpolar two-wire system
  2. Quiescent current: 0.5mA (bus); 6mA (power line)
  3. Action current: 2mA (bus); 15mA (power line)
  4. Operation indicator: The inspection indicator will blink once about every 1secondin the inspection status or remain lit in the operation status.
  5. Operating environment: Temperature: 10℃~50; relative humidity: 95%(40±2, without condensation)
  6. Terminaload: 4.7K resistance
  7. Externadimensions: 86×86×40(mm)
  8. Weight: about 119g
  9. Executive standard: GB16806-2006

Addressable output module AW-AIO2188-OUT




Features and technical parameters:

  1. Mode of operation: Nonpolar two-wire system
  2. Quiescent current: 0.6mA (power-down mode)
  3. Action current: 10mA
  4. Capacity of the output control contact: 2A@DC30V
  5. Operation indicator: The inspection indicator will blink once about every 1seconds in the inspection status or remain lit in the output status; the inpuindicator wilremain lit in the feedback status.
  6. Operating environment: Temperature: 1050; relative humidity: 95(40±2, without condensation)
  7. Terminaload: 47K resistance
  8. Externadimensions: 86×86×40(mm)
  9. Weight: about 130g
  10. Executive standard: GB16806-2006