Sabtu, 20 Juni 2015

AW Conventional Detector

Conventional photoelectrismoke detector
Item
Parameters
Operating Voltage Range:
to 32 VDC Volts Non-polarized
Standby Current:
100µA 24 VDC
Maximum Alarm Current (LED on: )
55mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Adjustable Sensitivity:
1-2.5%/FT
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Conventional fitemperature heat detector


Model No.: AW-CTD805

Item
Parameters
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Installation Temperatures:
14°F to 122°F (-10°C to50°C)
Operating Humidity Range:
10% to 93% RelativHumidity Non-condensing
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
40µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Fixed Temperature Rating:
135°F (57°C)

Conventional smoke and heat combined detector

Model No.: AW-CSH202


Item
Parameters
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
60µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Smoke    Sensitivity:
1.06±.26%FT.
Fixed Temperature Rating:
135°F (57°C)
Rate of Rise Detection:
Responds to greater than 15°F/min
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)



UV flame detector
AW-FD602-UV

SPECIFICATIONS
Operating Voltage Range:                    12 to 30 VDC Volts
Standby Current:                                  10 mA @ 24 VDC Alarm Current                                      30 mA @ 24 VDC Spectrum:                                           180~290nm
Detection Angle:                                 110 degree
Detection Sensitivity:                         Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol )
Relay Contact Load:                            1A@DC24V
Normal Status:                                     LED blinking in 5 seconds interval
Alarm Status:                                       LED lit steady
Protection rating:                                  IP 32
Operating Humidity Range:                10% to 93% Relative HumidityNon-condensing
Operating Temperature Range:          -10°C to 50°C (14°F to 122°FHeight:                                                 1.8˝ (45 mminstalled in BasDiameter:                                              4.0˝ (103 mm)


Weight:                                                 5.4 oz. (153g)

Kamis, 18 Juni 2015

AW Conventional

Conventional fire alarm control panel

Introduction:


1.    AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2.    It is modularized design, the panel can extend from 1 zonto 32 zones easily.
3.    It has 2 level control mode by lock
4.    It has 24VDC an5VDC power supply output.
5.    It has FIRE and FAULT signal output.
6.    It has 2 general sounderoutput.
7.    Each zone has 1 circuit detectorinput .
8.    Each zone can be disable by a button.
9.    It has RESET button treset the panel.
10.  It has SILENCE button to stop BUZZER and SOUNDERS.
11.  It has EVACUATE button to start manual fire alarm immediately.
12.  It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13.  It has an optional GSM modulfor fire alarm by SMS .
14.  It is economic, user-friendly and easy maintenance.
ITEM
1Zone panel
2Zone panel
4-8 Zone panel
12-32 Zone
panel
Model No.
AW-CFP2166-01
AW-CFP2166-02
AW-CFP2166-04
-8
AW-CFP2166-12-
32
Power specification

Mains supply voltage
110VAC or 240VAC
Internal power supply
27.2VDC
Total output current limited
500mA @
240VAC
500mA @
240VAC
3A @ 240VAC
3A @ 240VAC
Main supply monitor for fault
Yes
Battery protection for low voltage
Yes
Batteries (default configuration)
12V2AH*2
Detector circuit specification

Number of circuit
1
2
4-16
4-32
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Line fault monitor for detector
removal
Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes
Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted
to give Detector Removal Fault)
Call point resistor value
470 to 680  Ω , 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone
20 (based on a total detector current of 2mA, each detector consuming 100μ
A).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call
points per zone
No limit
Sounder circuit specification

Number of general circuits
2
End of line resistor value
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Outputs fused AT
400mA
Maximum number of bells @ 20mA
of each sounder output
20
Fuses

Battery fuse
1.5A F 20mm
Sounder outputs
500mA F 20mm
Fire and fault output