AW Addressable MCFA

Addressable Fire Alarm Panel AW-AFP2188


Features:

The AW-AFP2188 is a new type of analog fire alarm control panel which has 324 alarm control points (detectors and modules which are characterized by fully mixed coding, non-polarity and two buses). It complies with the provisions of both Fire Alarm Control Units (GB4717-2005) and Automatic Control System for Fire Protection (GB16806-2006).

Its characteristics are as follows:

  • The  intelligent  detectors  and  the  intelligent  modules  have  internal  microprocessors  to realize digital filtering and auto-compensation functions; the data collection is true and reliable; the AW-AFP2188 control panel can carry out data processing based on fuzzy control theory and modern fire alarm theory to fundamentally avoid missing alarms and to reduce false alarms, so as to improve reliability.
  • The detectors have a sensitivity setup function and can adjust the alarm sensitivity according to the specific environment and their influences.
  • The detecting bus and the control bus share a two-wire structure and have non-polarity and fully mixed coding of the detectors and modules, and the intelligent detectors and the intelligent modules can be directly connected to them, which greatly simplifies the system wiring, engineering installation and circuit maintenance.
  • The system uses an AC-DC master-standby power supply system which will automatically change between the master and standby power supplies in the event of a power failure of either of the two power supplies to ensure uninterrupted operation of the system.
  • The AW-AFP2188 can be connected to a special mini-printer to realize real-time printing.
  • The AW-AFP2188 can be connected to floor fire display panels to display fire alarms bstandard RS-485
  • The AW-AFP2188 can be connected to ten multi-line linkage control/monitoring points to control and monitor important equipment.
  • The AW-AFP2188 is equipped with eight bus manual control points, which makes it very easy for the user to control related equipment.
Order information:
  1. AW-AFP2188-100: 100 addresses panel
  2. AW-AFP2188-200: 200 addresses panel
  3. AW-AFP2188-324: 324 addresses panel

Repeater AW-RP2188

Features:

  • Each display panel is connected with a fire alarm control panel via a RS-48 bus. At most 99 display panels may be connected with each RS-485 bus.
  • The display panels can display fire alarm messages or feedback messages only rather than fault messages, action messages or other messages.
  • A fire alarm control panel may be used for setting the display area of a displapanel. The set display panel can display the fire alarm messages of the designated area (floor display) only. Note: See the Users Manual of the fire alarm control panel for the setting method.

Kamis, 18 Juni 2015

AW Conventional

Conventional fire alarm control panel

Introduction:


1.    AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2.    It is modularized design, the panel can extend from 1 zonto 32 zones easily.
3.    It has 2 level control mode by lock
4.    It has 24VDC an5VDC power supply output.
5.    It has FIRE and FAULT signal output.
6.    It has 2 general sounderoutput.
7.    Each zone has 1 circuit detectorinput .
8.    Each zone can be disable by a button.
9.    It has RESET button treset the panel.
10.  It has SILENCE button to stop BUZZER and SOUNDERS.
11.  It has EVACUATE button to start manual fire alarm immediately.
12.  It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13.  It has an optional GSM modulfor fire alarm by SMS .
14.  It is economic, user-friendly and easy maintenance.
ITEM
1Zone panel
2Zone panel
4-8 Zone panel
12-32 Zone
panel
Model No.
AW-CFP2166-01
AW-CFP2166-02
AW-CFP2166-04
-8
AW-CFP2166-12-
32
Power specification

Mains supply voltage
110VAC or 240VAC
Internal power supply
27.2VDC
Total output current limited
500mA @
240VAC
500mA @
240VAC
3A @ 240VAC
3A @ 240VAC
Main supply monitor for fault
Yes
Battery protection for low voltage
Yes
Batteries (default configuration)
12V2AH*2
Detector circuit specification

Number of circuit
1
2
4-16
4-32
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Line fault monitor for detector
removal
Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes
Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted
to give Detector Removal Fault)
Call point resistor value
470 to 680  Ω , 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone
20 (based on a total detector current of 2mA, each detector consuming 100μ
A).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call
points per zone
No limit
Sounder circuit specification

Number of general circuits
2
End of line resistor value
6.8k Ω ,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Outputs fused AT
400mA
Maximum number of bells @ 20mA
of each sounder output
20
Fuses

Battery fuse
1.5A F 20mm
Sounder outputs
500mA F 20mm
Fire and fault output