Sabtu, 20 Juni 2015

AW Conventional in-out

Entrance LED
Manual Call Point


Parameters
AW-CMC2166-1(Break glass)

  • Working voltage: 220VAC/50Hz or 24VDC
  • Maximum current5A (220VAC/50Hz) or 8A(24VDC)
  • Contactor resistance: 0.
  • Working temperature: -10~+50 
  • Relative humidity: max 93±2%

Alarm Bell




Model No.


Diameter


Work voltage
Work current  @
24VDC


Volume(dB)
AW-CBL2166-A-4
4 (100mm)
DC6V DC12V DC24V AC110V
AC230V



25  mA
85
AW-CBL2166-A-6
6(150mm)
95
AW-CBL2166-A-8
8(200mm)
97

AW-CBL2166-A-10
10(250mm)

100

Strobe Horn/Hooter


AW-CSS2166-2
Work Voltage
DC20V-DC30V
Work Current (average)
95mA
Flasintensity
1.2WS
Flascycle
<2.0s
Flasher life
30000times
Max alarm volume
100dB
Alarm voice
A: pokice car
B: Fire Truck ( default) C: Ambulance
Size
160*128*54mm
134*115*48mm

AW Conventional Detector

Conventional photoelectrismoke detector
Item
Parameters
Operating Voltage Range:
to 32 VDC Volts Non-polarized
Standby Current:
100µA 24 VDC
Maximum Alarm Current (LED on: )
55mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Adjustable Sensitivity:
1-2.5%/FT
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Conventional fitemperature heat detector


Model No.: AW-CTD805

Item
Parameters
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)
Installation Temperatures:
14°F to 122°F (-10°C to50°C)
Operating Humidity Range:
10% to 93% RelativHumidity Non-condensing
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
40µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Fixed Temperature Rating:
135°F (57°C)

Conventional smoke and heat combined detector

Model No.: AW-CSH202


Item
Parameters
Operating Voltage Range:
to 28VDC VoltNon-polarized
Standby Current:
60µA @ 24 VDC
Maximum Alarm Current (LED on: )
30mA 24 VDC
Operating Humidity Range:
10% to 93% RelativHumidityNon-condensing
Operating Temperature Range:
14°F to 120°F (-10°C to 49°C)
Smoke    Sensitivity:
1.06±.26%FT.
Fixed Temperature Rating:
135°F (57°C)
Rate of Rise Detection:
Responds to greater than 15°F/min
Height:
2.2˝ (55 mminstalled in Base
Diameter:
4.0˝ (103 mm)
Weight:
5.5 oz. (155 g)



UV flame detector
AW-FD602-UV

SPECIFICATIONS
Operating Voltage Range:                    12 to 30 VDC Volts
Standby Current:                                  10 mA @ 24 VDC Alarm Current                                      30 mA @ 24 VDC Spectrum:                                           180~290nm
Detection Angle:                                 110 degree
Detection Sensitivity:                         Grade I, 25m@flame (Container 33cmX33cm,Height 5cm with 2Kg ethanol )
Relay Contact Load:                            1A@DC24V
Normal Status:                                     LED blinking in 5 seconds interval
Alarm Status:                                       LED lit steady
Protection rating:                                  IP 32
Operating Humidity Range:                10% to 93% Relative HumidityNon-condensing
Operating Temperature Range:          -10°C to 50°C (14°F to 122°FHeight:                                                 1.8˝ (45 mminstalled in BasDiameter:                                              4.0˝ (103 mm)


Weight:                                                 5.4 oz. (153g)